Transport, short circuit or earthquake? When an SFRA test is worth running

Damage to the windings is not always visible from the outside. Frequency response analysis compares the transformer's fingerprint against a reference and can reveal deformation that other tests may not show.

Duration
30 seconds
Language
Spoken in Mexican Spanish
Captions
Spanish captions, switchable from the player
Published
Published September 18, 2026

What is behind this video

Three events subject a transformer to mechanical stress without leaving an external mark: transport, with its sustained vibration and acceleration; a through fault, whose electrodynamic forces act on the windings within milliseconds; and an earthquake. In all three the unit can go back to running normally and still have a displaced coil, a deformed winding or lost clamping pressure.

The difficulty is that the usual tests may not see it. Turns ratio and insulation resistance describe the electrical circuit and the state of the insulation, not the internal geometry. A deformed winding that has not yet failed electrically can pass both.

Frequency response works on something else. It injects a low-voltage signal across a wide frequency range and records how the winding responds. That response depends on the distributed capacitance and inductance of the assembly, which in turn depend on the physical position of the turns. The result is a curve — a fingerprint — that changes if the geometry changed.

Its usefulness is comparative: the curve is read against a reference. That can be a measurement of the same unit when it was sound, another phase of the same transformer, or a sister unit. Which is why a baseline taken while the unit is in good condition, before any event, is worth having: without it, interpretation rests on less direct comparisons.

The presenter in these videos is a character generated with artificial intelligence: the image and the voice do not belong to TEVKO personnel. The technical content and the figures quoted come from documented work and from the pages linked on each page.

Transcript — English translation

Has your transformer been moved, withstood a short circuit or been through an earthquake?

Damage to the windings is not always visible from the outside. Frequency response analysis compares the unit's fingerprint against a reference. And it can reveal deformation that other tests may not show.

If you have had an event like that, request the test at the email shown on screen.

Transcript — original Spanish audio

¿Tu transformador se trasladó, soportó un cortocircuito o pasó por un sismo?

Un daño en los devanados no siempre se ve por fuera. La prueba de respuesta en frecuencia compara la huella del equipo contra una referencia. Y puede revelar deformaciones que otras pruebas pueden no mostrar.

Si tienes un evento así, solicita la prueba al correo que aparece en pantalla.

The same Spanish captions ship as a WebVTT track inside the player. The contact shown on screen at the end of the video is ventas@tevko.com.

Questions this video answers

When is an SFRA test on a transformer worth running?

After transport, a short circuit or an earthquake. Those are the three events the video names, because they stress the windings mechanically without necessarily leaving an external sign.

What does frequency response detect that other tests may not show?

Winding deformation. The test compares the unit's fingerprint against a reference; internal damage that is invisible from the outside can appear in that comparison.

Related pages

Technical content reviewed by TEVKO Technical Management · last reviewed: September 17, 2026

Request a technical assessment

Write to our sales inbox with the following and we will tell you what the next step is:

  • The nameplate: rating, voltage, make and serial number.
  • The location of the installation.
  • The problem the unit presents, or the event that occurred.
ventas@tevko.com