The gas relay or the pressure relief valve operated: what to do before re-energising

If the gas relay or the pressure relief valve operated, it is worth diagnosing the transformer before energising it again: re-energising with an internal fault can aggravate damage that was still repairable.

Duration
33 seconds
Language
Spoken in Mexican Spanish
Captions
Spanish captions, switchable from the player
Published
Published September 18, 2026

What is behind this video

The gas relay and the pressure relief valve are not process alarms: they are protections that respond to what happens inside the tank. The relay accumulates gas released by internal activity or reacts to a sudden surge of oil; the valve relieves pressure when something builds it abruptly. Their operation means an event occurred inside the transformer, even if nothing shows on the outside and the unit looks ready to go back.

The pressure to restore service pushes the other way. Re-energising is quick, costs nothing up front and sometimes works. The risk is asymmetric: if the internal fault is still there, energising subjects the weak point to dielectric and thermal stress again, and localised damage — which could have been repaired — can become extended damage to the winding or the core.

Three things are worth gathering before deciding. The nameplate, with rating, voltage, make and serial number, which defines which tests apply. Photographs of the unit, the oil level and the indicators, which show whether there was fluid loss, deformation or visible discharge. And a record of which protections operated and in what order, which narrows down the type of event.

With that information the next step can be defined: which tests come first, whether an oil sample for dissolved gas analysis is warranted, and whether the diagnosis can be done on site or the unit has to be moved.

The presenter in these videos is a character generated with artificial intelligence: the image and the voice do not belong to TEVKO personnel. The technical content and the figures quoted come from documented work and from the pages linked on each page.

Transcript — English translation

Did the gas relay or the pressure relief valve on your transformer operate?

Before energising it again, it is worth diagnosing it. Re-energising with an internal fault can aggravate damage that was still repairable.

Send the nameplate, photos of the unit and of the oil level, and which protections operated. With that information the next step gets defined.

Write to the email shown on screen.

Transcript — original Spanish audio

¿Operó el relevador de gas o la válvula de sobrepresión de tu transformador?

Antes de volver a energizarlo, conviene diagnosticarlo. Reenergizar con una falla interna puede agravar un daño que todavía era reparable.

Envía la placa, fotos del equipo y del nivel de aceite, y qué protecciones operaron. Con esa información se define el siguiente paso.

Escríbenos al correo que aparece en pantalla.

The same Spanish captions ship as a WebVTT track inside the player. The contact shown on screen at the end of the video is ventas@tevko.com.

Questions this video answers

Can a transformer be re-energised after the gas relay operated?

It is worth diagnosing it first. The video puts it plainly: re-energising with an internal fault can aggravate damage that was still repairable.

What information should be gathered before deciding?

The nameplate, photos of the unit and of the oil level, and a record of which protections operated. With those the next step gets defined. Send them to ventas@tevko.com.

Related pages

Technical content reviewed by TEVKO Technical Management · last reviewed: September 17, 2026

Request a technical assessment

Write to our sales inbox with the following and we will tell you what the next step is:

  • The nameplate: rating, voltage, make and serial number.
  • The location of the installation.
  • Photos of the unit and the oil level, and which protections operated.