TEVKO, transformadores y subestaciones de potencia

Video

Moisture in transformer paper insulation

Duration
32 seconds
Language
Spoken in English
Captions
English captions, switchable from the player
Published
Published November 12, 2026

What is behind this video

A mine transformer's oil can test dry and the unit can still be wet. It is not a lab error: close to 99% of the moisture sits in the paper, not the oil. The paper releases water when hot and soaks it back when cold. Sample it cold and the number can look fine while the paper is still wet.

Not necessarily. The water does not mostly live in the oil; it lives in the paper. Close to 99% of the moisture sits in the cellulose, according to Vaisala. A low oil result can coexist with paper that is still wet, especially if the sample was taken cold, when the paper holds the water.

The paper acts like a sponge. When it is hot it releases water into the oil; when it is cold it soaks that water back. The same unit can therefore give a different number depending on the sample temperature. Reading the report without that temperature leads to an incomplete view of the solid insulation.

When the unit is cold the paper holds the water and the oil can look dry, with a number that appears favorable. The video warns about exactly that: a good-looking result does not prove the paper is dry. Moisture in oil has to be read together with the sample temperature, not as a verdict on its own.

The references behind what the video says are: Vaisala: close to 99% of the moisture sits in the paper / cellulose.

This piece is animation and typography: it does not show TEVKO personnel. The figures are the ones in the script and can be checked against this page and the linked pages.

Transcript — English audio

A mine's transformer oil tested dry, and the transformer can still be wet. It's not a lab error.

The water doesn't live in the oil. It lives in the paper.

Close to 99 % of the moisture sits in the cellulose. The paper is a sponge: hot, it releases water into the oil; cold, it soaks it back.

That's why the result changes with the sample temperature. But watch out: sample it cold and the number looks great, with the paper still wet.

So it's not dry oil. It's wet paper. Comment MOISTURE and we'll tell you how to read your report.

The same captions ship as a WebVTT track inside the player. The spoken close invites a comment on the network where the video was posted. On this page the contact is ventas@tevko.com and the phone +52 33 2101 7241.

Questions this video answers

Does dry transformer oil mean the transformer is dry?

Not necessarily. The water does not mostly live in the oil; it lives in the paper. Close to 99% of the moisture sits in the cellulose, according to Vaisala. A low oil result can coexist with paper that is still wet, especially if the sample was taken cold, when the paper holds the water.

Why does the moisture-in-oil result change with temperature?

The paper acts like a sponge. When it is hot it releases water into the oil; when it is cold it soaks that water back. The same unit can therefore give a different number depending on the sample temperature. Reading the report without that temperature leads to an incomplete view of the solid insulation.

What is the risk of sampling the oil when it is cold?

When the unit is cold the paper holds the water and the oil can look dry, with a number that appears favorable. The video warns about exactly that: a good-looking result does not prove the paper is dry. Moisture in oil has to be read together with the sample temperature, not as a verdict on its own.

Related pages

Technical content reviewed by TEVKO Technical Management · last reviewed: November 12, 2026

Request a technical assessment

Write to our sales inbox with the following and we will tell you what the next step is:

  • The nameplate: rating, voltage, make and serial number.
  • The location of the installation.
  • The problem the unit presents, or the event that occurred.
ventas@tevko.com