TEVKO
Transformer oil and dissolved gas analysis (DGA), TEVKO

Technical blog

How to interpret transformer oil analysis and DGA

The oil tells the internal story of the transformer. Learn to read DGA and physicochemical parameters to anticipate failures before they happen.

A transformer's dielectric oil is much more than insulation and coolant: it is a chemical record of what happens inside. Reading it correctly lets you detect incipient faults — overheating, arcing, partial discharge — while the equipment keeps running, weeks or months before they show as a visible failure.

Dissolved gas analysis (DGA) quantifies the gases the insulation generates under stress: hydrogen, methane, ethylene, acetylene, carbon monoxide and dioxide. Each fault type leaves a distinct signature, interpreted with key gas, Doernenburg and Rogers ratios and the Duval triangle, under IEEE C57.104 and IEC 60599.

Acetylene signals high-energy arcing; hydrogen with methane, partial discharge; ethylene, severe overheating. But the absolute value matters less than the trend: an increasing gas generation rate (ppm/day) is the real alarm.

The physicochemical analysis complements DGA: dielectric strength, moisture, acidity, interfacial tension and color tell whether the oil needs filtering, regeneration or replacement.

At TEVKO we don't just deliver numbers: we sample with a protocol that avoids contamination, interpret against the asset's history and recommend action — monitor, reduce load, schedule an internal inspection. The trend, not a single value, drives the decision.

Frequently asked questions

What does dissolved gas analysis detect?

Incipient internal faults from the gases dissolved in the oil: acetylene indicates high-energy arcing; hydrogen and methane, partial discharge; ethylene, severe overheating. It is done without de-energizing.

How often should DGA be done?

For critical power transformers, at least annually, and more often with anomalous trends. The key is the gas generation rate between samples, not an isolated value.

What methods are used to interpret it?

Key gas, Doernenburg and Rogers ratios and the Duval triangle, per IEEE C57.104 and IEC 60599, combined and contrasted against the transformer's history.

Does the transformer need an outage?

No. The oil sample is taken energized, with a protocol that avoids air contamination — one of DGA's advantages over electrical tests that require an outage.

Related tests and services

Talk to a transformer specialist

Tell us about your asset and we'll respond with a diagnosis and a tailored quote — not generic pricing.